Several wiring installation standards apply to hazardous areas, led by IEC 60079-14 for design, selection and erection.
| IEC 60079-0: 2011 | Explosive atmospheres: Part 0. General Requirements. |
| IEC 60079-14: 2007 | Explosive atmospheres: Part 14. Electrical installations design, selection and erection |
| IEC 60079-14: 2013 BS EN 60079-14: 2014 | Explosive atmospheres: Part 14. Electrical installation design, selection and erection |
| BS EN 50262: 1999 | Metric cable glands for electrical installation |
| BS 6121-5: 2005 | Mechanical cable glands. Code of practice for selection, installation and inspection of cable glands and armour glands. |
Other installation rules may apply to a particular installation.
- BS 7671- Requirements for electrical installations. IEE Wiring Regulations
- IEC 60364 – Electrical Installations of Buildings
- IEC 60092 – Electrical installations in ships
- Company or Customer specifications
How the wiring installation standards fit together #
IEC 60079-14 is the core document for hazardous areas. It covers design, selection and erection of electrical installations, including cable types, glands, earthing and the extra rules for each protection concept. Its companion, IEC 60079-17, covers inspection and maintenance once the installation is in service.
However, other wiring installation standards still apply alongside it. General rules for buildings come from IEC 60364 or national wiring regulations such as BS 7671. Ships follow IEC 60092, and offshore units often apply class society rules as well. Cable gland standards, such as BS EN 50262 for metric glands, set dimensional and performance requirements.
Finally, owners and contractors frequently add their own company specifications, which may be stricter than the standards. As a result, always confirm which documents are contractual before you start. For practical guidance, see Ex cable glands and competent persons. The IEC standards are available from IEC.