Pressurised enclosures must be strong, well sealed and interlocked so that overpressure is reliably maintained.
The minimum IP rating for pressurised enclosures is IP4X (IP 3X for alarmed pz enclosures),
Not all enclosures are suitable for pressurisation, but the seals may only be designed to
prevent entry of contaminants, not to maintain an over-pressure within the enclosure.
Enclosures must therefore be appropriately designed, be strong enough to withstand impact tests
and internal over-pressure, and have effective and correctly oriented seals.
The enclosure ducts shall be capable of withstanding a minimum overpressure of 200Pa (2mBar). They must also withstand an over-pressure equivalent to 1.5 times the maximum working over-pressure, or the maximum over-pressure with all outlet ducts closed.
Enclosure covers/doors #
Where the interior of a type px enclosure can be accessed via doors/covers without the use of tools or keys, an interlock is required to automatically de-energise the electrical supply when the door/cover is opened.
Doors/covers must display the warning: “Do not open when an explosive atmosphere may be present”.
When pressurised enclosure contains components which have hot surfaces, or are energy-storing (e.g. capacitors), doors/covers should be fitted with warning notices which state the necessary time delay after isolation of the supply before opening the covers.
Maintaining pressurised enclosures #
A pressurised enclosure only protects equipment while it holds pressure, so its seals are as important as its control system. Every door, gland and penetration must seal well enough to keep the leakage rate within the design value. Damaged gaskets, missing plugs or extra holes quickly reduce overpressure and may trigger alarms or trips.
Doors also need discipline. Where a px enclosure can be opened without tools, an interlock must cut power when the door opens. In addition, warning labels remind staff not to open the enclosure while a flammable atmosphere may be present, and to wait for any marked cool-down or discharge time after isolation.
During inspection, check seals, door interlocks, labels, ducts and the strength of any modified panels. For related topics, read pressurisation safety devices and techniques of pressurisation. Design rules for pressurised enclosures are set out in IEC 60079-2, published by IEC.