EPL Gb is the equipment protection level for equipment that is safe in normal operation and expected faults, suitable for Zone 1.
Zones of Use: Increased Safety equipment may be used in Zones 1 & 2, unless a risk assessment, taking into account the possible consequences of an explosion, indicates differently.
Ambient Conditions:
-20°C to +40°C, unless otherwise marked.
What EPL Gb means for selection #
The equipment protection level, or EPL, describes how likely equipment is to become an ignition source. EPL Gb means a high level of protection: the equipment is not an ignition source in normal operation or during expected malfunctions. That makes it suitable for Zone 1, where a flammable atmosphere is likely to occur occasionally, and for Zone 2.
Increased safety equipment to level eb is rated Gb. On an area classification drawing that shows EPLs, look for Gb or Gc to confirm it can be used. Where the drawing shows only zones, the usual mapping applies: Zone 1 requires Gb and Zone 2 requires Gc, unless a risk assessment sets a different level.
Check the ambient range as well. Unless marked otherwise, Ex e equipment is designed for minus 20 °C to plus 40 °C, and equipment for hotter or colder sites carries a specific marking. Many offshore and tropical sites need a wider range, so confirm it before ordering.
For context, read increased safety and Ex equipment selection. AZUVIA ECHLORX is marked Ex eb ib IIC T6 Gb under the IECEx scheme.