Combined methods of protection, or hybrid protection, use more than one explosion protection concept in a single piece of equipment.
Introduction #
Electrical equipment may be manufactured with more than one method of explosion protection. Equipment of this type has combined methods of protection but may also be known as a hybrid.
This approach combines the best features of each type of protection in to one piece of equipment, for both economic and practical purposes.
Hybrid equipment may be constructed using any combination of the various methods of explosion protection and the equipment will be marked with the symbolic letters and construction standard numbers relative to the types of explosion protection used.
Probably the most commonly used combination uses ‘d’ and ‘e’ types of equipment, and the table below shows current and older standards for these only.
Hybrid equipment must also be installed and maintained in accordance with the relevant standards.
Standards #
| IEC & BS EN60079-1: 2014 | Flameproof enclosures ‘d’ |
| IEC & BS EN60079-7: 2015 | Increased safety enclosure ‘e’ |
| IEC60079-0: Ed.6: 2011 BS EN60079-0: Ed.6: 2012 | Explosive atmospheres – Part 0: Equipment – General requirements |
| IEC60079-14: 2013 BS EN60079-14: 2014 | Electrical equipment for explosive gas atmospheres: Part 14. Electrical installations in hazardous areas (other than mines) |
| IEC60079-14: 2013 BS EN60079-17: 2014 | Electrical equipment for explosive gas atmospheres: Part 17. Inspection and maintenance of electrical installations in hazardous areas (other than mines) |
When to use combined methods of protection #
Combined methods of protection let designers put each component in the most practical form of protection. A motor control station, for example, can house sparking contactors in a flameproof chamber while using an increased safety terminal box for the field wiring. As a result, cable entry is simpler, the enclosure is lighter and maintenance is easier.
The equipment label lists each method used, such as Ex de IIB T4 Gb. Installers and inspectors must then apply the rules for every concept present. For instance, the flameproof part needs intact flamepaths and correct bolts, while the increased safety part needs certified glands, correct terminal loading and good IP seals.
Typical hybrid products include control stations, light fittings, motors and telephones. For examples, read Ex deq light fittings and hybrid protection marking. Hybrid equipment is certified through schemes such as the IECEx scheme.