Oxygen enrichment makes flammable atmospheres easier to ignite and more violent when they burn.
Oxygen Enrichment #
The normal oxygen content in the atmosphere is around 20.95%. If a location has a value which exceeds this, its atmosphere is said to be oxygen enriched.
E.g.: – gas manufacturing plants, hospital operating theatres, & around oxy-acetylene equipment.
Oxygen enrichment has three disadvantages #
1. It can lower the ignition temperature of flammable materials as shown:
| Material | Air | Increased Oxygen |
| Ignition temperature °C | Ignition Temperature °C | |
| Hydrogen Sulphide | 260 | 220 |
| Acetylene | 305 | 296 |
| Ethane | 515 | 506 |
2. Oxygen enrichment significantly raises the upper explosive limit (UEL) of the majority of gases and vapours, thereby widening their flammable range:
| Materials | Air | Increase Oxygen | ||
| LEL% | UEL% | LEL% | UEL% | |
| Methane | 4.4 | 17.0 | 5.2 | 79 |
| Propane | 1.7 | 10.9 | 2.3 | 55 |
| Hydrogen | 4.0 | 77.0 | 4.7 | 94 |
3. It can allow an atmosphere to be ignited with much lower values of electrical energy.
Explosion protected equipment will have been tested in normal atmospheric conditions. Equipment for use in an oxygen enriched atmospheres must be specially tested and certified.
Managing oxygen enrichment risks #
Oxygen enrichment changes the rules on which Ex equipment is based. Standard tests assume normal air with about 21 percent oxygen. With more oxygen, gases ignite at lower temperatures and with less energy, and they burn over a wider range of concentrations. Equipment that is safe in air may therefore become an ignition source.
Enriched atmospheres can occur near oxygen storage and supply systems, in oxy-fuel cutting areas, in medical settings and in some process plants. Leaks from oxygen lines are especially dangerous because they are invisible. As a result, ventilation, leak detection and good housekeeping are important, along with keeping oil and grease away from oxygen fittings.
Where enrichment cannot be ruled out, equipment must be specially assessed and certified for those conditions. For related topics, read theory of combustion and ignition sources. General requirements for Ex equipment are set out in IEC 60079-0, published by IEC.