Increased safety design prevents arcs, sparks and hot surfaces from occurring inside or outside the equipment.
Design Features #

Principle and design
The safe operation of Increased Safety equipment depends on the prevention of any source of ignition (excessive surface temperatures, arcs or sparks) internally or externally.
Some of the special design features that are incorporated to achieve this include: –
- Ingress protection against solid objects and water – at least IP 54 for enclosures containing live parts (IP44 if all internal parts are insulated).
- Mechanically strong enclosure resistant to impact. Test conditions differ for equipment for use where risk of damage is HIGH, or LOW (‘X’ certificate).
- Terminals manufactured from high quality insulation material.
- Specified creepage and clearance distances incorporated in the design of terminals.
- Terminal locking devices to ensure conductors remain secure in service.
- Certified de-rating of terminals.
- Terminal population of enclosure limited by circuit design.
- Close excess current circuit protection.
Increased safety design in practice #
Increased safety design works by removing ignition sources rather than containing them. There is no flameproof enclosure; instead, every connection, insulation material and surface is designed to stay cool and secure. That is why the details matter so much: terminal type, conductor size, number of wires per terminal and the heat produced by each circuit.
Terminal population and de-rating are two of the most important rules. The certificate limits how many terminals and conductors may be fitted, and at what current, so that the enclosure never becomes too hot. Adding terminals or increasing load beyond the certificate can push surface temperatures above the T class.
For maintenance staff, the lesson is simple: replace parts like for like and follow the certificate. For more detail, read increased safety terminals and Ex e inspection. AZUVIA’s ECHLORX uses increased safety construction and is certified under the IECEx scheme.