The principles of intrinsic safety rely on keeping electrical energy too low to ignite a flammable atmosphere.
Intrinsically Safe circuits achieve safety by maintaining very low energy levels so that hot surfaces will not be produced, and any electrical sparks will not have sufficient energy to ignite the most easily ignitable concentration of a flammable mixture.
This is achieved by limiting the voltage and current supplied to the equipment in the hazardous area. These levels of voltage and current must not be exceeded under normal or fault conditions.
The circuit parameters, voltage, current, resistance, inductance and capacitance are factors considered during the design of IS circuit.
The standards give the required data in tables, and in graphical form (the characteristic ignition curves), for Group 1 and Group II subdivision IIA, IIB & IIC gases.
Applying the principles of intrinsic safety #
Intrinsic safety is unique among protection methods because it protects the whole circuit rather than a single enclosure. If energy is kept low enough, even a broken wire or a short circuit cannot produce an igniting spark. As a result, IS is the preferred method for instrumentation, and technicians can often work on live circuits without gas-free certificates.
The limits depend on the gas. Hydrogen and acetylene, in group IIC, ignite with very little energy, so IIC circuits have the tightest limits. Ignition curves in the standards show the maximum safe current for a given voltage, and the circuit’s capacitance and inductance must also stay within limits, because they store energy that could be released as a spark.
Designers prove safety with the entity concept, comparing source and load parameters. For the next steps, read IS parameters and IS system layout. AZUVIA’s ECHLORX uses intrinsic safety for parts of its control circuits and is certified under the IECEx scheme.