Docs Category: Explosion Proof Basics

System of earthing arrangements

Earthing arrangements determine how fault currents flow and are a key part of safe electrical installations in hazardous areas. Electrical earthing or circuit protective conductors (CPC) Conductors installed to provide a low impedance path for the current which flows under fault…

Read More

Ex p[i] (Hybrid)

Ex p(i) hybrid protection lets associated intrinsically safe apparatus sit in a hazardous area inside a pressurised enclosure. The parts(s) of an IS system which are marked to indicate that they should be installed in a non-hazardous area (associated equipment [Ex…

Read More

Restriction of Installation

Restriction of installation rules limit where and how electrical equipment and wiring may be placed in hazardous areas. Types of lamps in Ex e and Ex n luminaires There are restrictions in the IEC60079-14 installation standard on the type of lamps…

Read More

Ex pde (Hybrid)

Ex pde hybrid protection covers equipment inside a pressurised enclosure that must stay energised when overpressure is lost. Enclosure using protection by pressurisation type ‘p’, may have internal equipment which have to remain energised in the absence of overpressure. Such equipment…

Read More

Other installation requirements

These hazardous area installation requirements cover cable routing, unused cores, conductor ends and intrinsically safe cabling. Particular IEC60079-14 installation requirements from the standards Cables and terminations: Cable routing. Where cables pass from one safe area to another via a hazardous area,…

Read More

Ex e im (Hybrid)

Ex e im hybrid protection combines increased safety, intrinsic safety and encapsulation in a single piece of equipment. An enclosure may have an encapsulated component inside. A typical example is a telephone for use in a hazardous location. The casing of…

Read More

Light Fittings – Ex deq / Ex dem

Ex deq light fittings combine several protection concepts so that lighting can be used safely in hazardous areas. The lighting fitting illustrated below employs three protection concepts, i.e. increased safety type ‘e’, flameproof type ‘d’ and powder filing ‘q’. This type…

Read More

Cable Glands

Ex cable glands maintain the type of protection where cables enter equipment in a hazardous area. Cable glands are used when terminating cables into electrical equipment. They must be selected according to the methods of explosion protection employed and the environmental…

Read More

Markings and Certification

Hybrid protection marking shows every protection method used in a piece of equipment, along with its group and temperature class. Where different types [levels] of protection are employed for different parts of electrical equipment or component, the Ex marking will include…

Read More

Cold Flow

Cold flow in cables is the slow creep of some insulation materials under pressure, which can loosen cable glands in hazardous areas. Certain materials used in the manufacture of cables are susceptible to a condition known as ‘cold flow’. Cold flow…

Read More

Jointing of Cables

Jointing of cables in hazardous areas should be avoided where possible and, when needed, must keep the installation safe. In hazardous areas, wherever possible, cable runs should be continuous and without interruption. Where discontinuity cannot be avoided, the joint, in addition…

Read More

Fixed Equipment in Zones 1 and 2

Fixed equipment in Zones 1 and 2 must be selected and installed to match the zone, gas group and temperature class. IEC 60079-14 specifies the cable requirements for fixed equipment in Zone 1 & 2. Cables sheathed with thermoplastic, thermosetting or…

Read More

Combined (Hybrid) Methods of Protection

Combined methods of protection, or hybrid protection, use more than one explosion protection concept in a single piece of equipment. Introduction Electrical equipment may be manufactured with more than one method of explosion protection. Equipment of this type has combined methods…

Read More

Special Protection (Ex “s”)

Ex s special protection covers equipment that is safe in hazardous areas but does not fit any of the standard protection concepts. Special protection “s” allows a design concept that cannot comply in full with recognised type of protection or where…

Read More

Levels of Protection

Encapsulation levels of protection ma, mb and mc define how many faults Ex m equipment can tolerate and where it may be used. Encapsulated equipment may be manufactured with EPL ‘ma’, mb’ or ‘mc’. ‘ma’ – must not be capable of…

Read More

Cables

Hazardous area cables must suit the zone, the protection concept and the conditions they will meet in service. Electrical equipment in hazardous areas may be weird using cable having metallic or non-metallic sheath, or weird in conduit. Today, cable is generally…

Read More

Principle and Construction

The encapsulation principle seals ignition sources inside a compound so an explosive atmosphere cannot reach them. Principle With this type of protection the encapsulant, typically a thermosetting epoxy resin or thermoplastic, elastomeric material, establishes a complete barrier between any surrounding flammable…

Read More

Competent Persons

Competent persons are the only people who should select, install or maintain electrical equipment in hazardous areas. Technicians, or operatives as they are called in the IEC60079-14 standard, are required to have sufficient knowledge to achieve the correct selection and installation…

Read More

Standards

Several wiring installation standards apply to hazardous areas, led by IEC 60079-14 for design, selection and erection. IEC 60079-0: 2011 Explosive atmospheres: Part 0. General Requirements. IEC 60079-14: 2007 Explosive atmospheres: Part 14. Electrical installations design, selection and erection IEC 60079-14:…

Read More

Encapsulation (Ex m/ EEx m)

Ex m encapsulation protects small components by enclosing them in a compound that keeps flammable gas away. The method of protection, encapsulation, is used mainly for smaller items of equipment such as solenoid coils and electronic components. Standards IEC 60079-18: 2009…

Read More

Construction

Powder filling construction rules set the IP rating, filling material and clearances needed for Ex q equipment. The minimum ingress protection for this type of protection is IP54, but equipment constructed to provide IP55 must be fitted with a breathing device….

Read More

Powder Filling Principle

The powder filling principle relies on fine granules to stop a flame from spreading out of Ex q equipment. The filling, which may be quartz or glass particles, achieves safety by what is known as “suppression of flame propagation”. The flammable…

Read More

Powder filling (Ex q / EEx q)

Ex q powder filling protection surrounds ignition sources with fine granules so they cannot ignite the surrounding atmosphere. The explosion protection concept powder filling is used in applications such as capacitors and ballast units in Increased Safety Ex ‘deq’ lighting fittings,…

Read More

Construction

Oil immersion construction rules make sure Ex o equipment keeps its ignition sources fully covered by protective liquid. A breather is fitted to the enclosure to allow release of the flammable gases produced during arc quenching, preventing the build-up of these…

Read More

Oil Immersion Principle

The oil immersion principle keeps sparking and hot parts under a protective liquid so flammable gas cannot reach them. The oil level in the equipment is used to completely cover components which arc/spark or produce hot surfaces during normal operation, establishing…

Read More

Oil-immersion Ex o / EEx o

Ex o oil immersion protection is used mainly for heavy-duty transformers and switchgear in hazardous areas. Oil-immersion is typically used for heavy duty transformers and switchgears. Standards Current constructional standards IEC 60079-6: 2007 BS EN60079-6: 2007 Explosive Atmospheres – Part 6:…

Read More

Inspection

Intrinsic safety inspection confirms that IS equipment, barriers and cabling still match their certification and documentation. Inspection When inspecting Ex I installations, pay particular attention to the following points:- The components of the installation must be certified I.S., unless identified as…

Read More

Maintenance and Testing

IS maintenance and testing must preserve the energy limits that make an intrinsically safe circuit safe. After an installation is commissioned and the “as-built” drawings are issued, no unauthorised modifications may be made to the system. Any changes found necessary must…

Read More

Installation of I.S. equipment

The installation of IS equipment must keep intrinsically safe circuits separate and protected from other circuits. The components of an IS installation (field equipment and associated apparatus), must to be certified items which comply with the standards. The documentation will include…

Read More

Marking

Intrinsic safety marking shows whether equipment is field apparatus or associated apparatus, and its level of protection. Associated apparatus not suitable for installation in a hazardous area will be certified and marked with the Ex symbol and the type of protection,…

Read More

Surge Suppression

Surge suppression protects intrinsically safe instrument loops from transients caused by power faults and lightning. Electronic equipment and instrumentation are always at risk from surges and transients caused by power faults or nearby lightning strikes. Surge suppression devices (transient voltage suppressors…

Read More

I.S. Parameters

IS parameters are the voltage, current, power, capacitance and inductance values used to prove an intrinsically safe loop is safe. Main power supply voltage (Um) Um (max. rms AC or DC voltage) refers to the maximum voltage that can be applied…

Read More

Galvanically Isolated Barriers

Galvanically isolated barriers limit energy into the hazardous area without a direct electrical connection to the safe area. Galvanically Isolated Barriers Devices which overcome the limitations of zener barrier are called isolation interfaces. Typically, the isolation required may be achieved by…

Read More

The Zener Barrier

A zener barrier limits the voltage and current that can reach intrinsically safe equipment in a hazardous area. The Zener Barrier (also know as shunt diode barrier): The Zener barrier interface is normally located in the safe area, close to the…

Read More

Typical I.S. system layout

A typical IS system layout links safe-area equipment to field devices through an energy-limiting interface. An IS system usually consists of safe area equipment, a safe to hazardous area interface, cables and junction boxes, and field (hazardous area) equipment. The system…

Read More

Basic Principles of IS

The principles of intrinsic safety rely on keeping electrical energy too low to ignite a flammable atmosphere. Intrinsically Safe circuits achieve safety by maintaining very low energy levels so that hot surfaces will not be produced, and any electrical sparks will…

Read More

Levels of Protection

Intrinsic safety levels of protection ia, ib and ic set how many faults equipment can tolerate and where it may be used. Level of protection EPL ATEX Category Zones of use ** Ia Ga 1G Zones 0,1 & 2 Ib Gb…

Read More

Intrinsic Safety (Ex i)

Intrinsic safety (Ex i) is the protection concept most widely used for instrumentation in hazardous areas. Introduction Intrinsic Safety (I.S) is a low energy signalling technique that prevent explosion by ensuring that the energy transferred to a hazardous area is well…

Read More

Marking

Pressurisation marking shows the type of pressurisation used and whether a control system is associated equipment. The equipment marking must be to IEC 60079-2 & IEC 60079-0, and contain the following information: The manufacturers name Model number, type and serial number…

Read More

Temperature Limits

Pressurisation temperature limits decide the temperature class of a pressurised enclosure and its internal components. Type px or type py pressurisation The temperature class shall be based on the higher of the hottest external surface of the enclosure or the hottest…

Read More

Equipment Energised During Absence of Overpressure

Equipment energised without overpressure must have its own explosion protection because pressurisation no longer protects it. An anti-condensation heater may be used in a rotating electrical machine to prevent internal surfaces and atmosphere becoming cold, thereby preventing the formation of moisture…

Read More

Externally Mounted Electrical Equipment

Externally mounted equipment on a pressurised enclosure must be protected for the zone in which the enclosure sits. Electrical equipment mounted on the exterior of a pressurised enclosure must be explosion protected in accordance with the Zone (or EPL requirement) in…

Read More

Action on Loss of Pressure

The required action on loss of pressure depends on the zone and on what equipment is inside the pressurised enclosure. No internal source of release The over-pressure within the enclosure is monitored by a pressure switch/sensor, and a flow-rate switch/sensor, located…

Read More

Techniques of Pressurisation

There are three main techniques of pressurisation: static, leakage compensation and continuous flow. The applicable pressurising techniques depend upon the condition and on the constituents of the release as follows: Static pressurisation. Pressurisation with continuous flow; Pressurisation with leakage compensation; Pressurisation…

Read More

Controls & Safety Devices

Pressurisation safety devices monitor overpressure and flow so the enclosure is only energised when it is safe. The level of overpressure will be monitored by a pressure sensor or switch located in the enclosure,at the most difficult point at which to…

Read More

Pressurised Enclosures

Pressurised enclosures must be strong, well sealed and interlocked so that overpressure is reliably maintained. The minimum IP rating for pressurised enclosures is IP4X (IP 3X for alarmed pz enclosures), Not all enclosures are suitable for pressurisation, but the seals may…

Read More

Ducts

Pressurisation ducts carry protective gas into and out of the enclosure and must be routed and built with care. Ducts The entry of the inlet duct should be positioned in a non-hazardous location wherever possible (unless from cylinders). The exhaust duct,…

Read More

Protective Gas

The protective gas keeps flammable gas out of a pressurised enclosure, so its source and quality are critical. The protective gas is normally air, but for certain applications may be an inert gas such as nitrogen. When air is the protective…

Read More

Purging

Purging removes any flammable gas from a pressurised enclosure before its electrical equipment is energised. Purging involves passing a specified quantity of the safe gas through the enclosure in order to remove any flammable gases which may have entered. The standards…

Read More

Principles of Operation

The principles of pressurisation rely on keeping an enclosure slightly above outside pressure so flammable gas cannot enter. The basic principle of operation involves raising and maintaining the internal pressure of the enclosure to a level slightly above the atmospheric pressure…

Read More

Types of pressurisation and EPL

The types of pressurisation px, py and pz differ in how far they reduce the hazard inside the enclosure. Type pxb is a type of pressurised enclosure that provides an equipment protection level Gb (or Mb or Db). This means that…

Read More

Applications

Pressurisation applications range from small instrument cabinets to large motors and whole control rooms. Pressurisation can provide explosion protection for a wide range of instrumentation or electrical equipment – there is no limit to size, within reason, which can be accommodated….

Read More

Pressurised Equipment

Pressurised equipment keeps flammable gas out by holding a protective gas inside the enclosure above outside pressure. Introduction Pressurisation is a simple explosion protection technique. If the interior of an enclosure is at a pressure slightly above that externally, any flammable…

Read More

Summary of Type ‘n’ Equipment Variations

This summary of type n equipment variations shows how nA, nC, nL and nR relate to newer protection codes. This table summarises the variations in Type ‘n’ Equipment Type ‘n’ equipment variation Marking Energy limited equipment “nL” replaced by ‘ic’ Protected…

Read More

Cable Glands

Type n cable glands must be certified and, for Ex nR equipment, maintain the enclosure’s restricted breathing. Ex ‘n’ gland certification etc. According to IEC60079-14, cable glands for Ex n (and for Ex e) must be certified as meeting the requirements…

Read More

Marking

Type n equipment marking tells you which method is used to control sparks and hot surfaces in Zone 2 equipment. The above table shows the marking on Type ‘n’ equipment to indicate the method applied to either eliminate or control spark…

Read More

Additional Protection Measures

Type n additional protection measures allow sparking or hot components to be used safely in Zone 2 equipment. Additional protection measures The additional protection measures included for components which produce arcs/sparks or hot surfaces are explained below: Energy limited equipment and…

Read More

Principle and Design

Type n design prevents ignition sources in normal operation using features similar to increased safety equipment. Type ‘n’ protection is similar in concept to increased safety type ‘e’ protection, and the design features ensure that, in normal operation, sources of ignition…

Read More

Type ‘n’ Protection

Type n protection is a cost-effective explosion protection concept for equipment used in Zone 2. Definition Type ‘n’ protection is a type of protection applied to electrical equipment such that in normal operations and in certain specified regular expected occurrences, it…

Read More

Increased Safety Ex e Motors

Ex e motors are induction motors designed so that no part becomes hot enough to cause ignition, even when stalled for time tE. Increased Safety Ex e Motors These motors are similar in appearance to standard industrial motors and inspection of…

Read More

Installation, Inspection and Maintenance

Ex e inspection and maintenance keep increased safety equipment within its certified condition throughout its life. Increased safety is a simple concept, but there are many detailed requirements that must be correctly implemented to result in a safe installation! To comply…

Read More

Increased Safety Terminals

Increased safety terminals are designed and loaded so that connections stay cool and secure in service. Introduction The terminal installed in an increased safety enclosure must be ‘component certified’. They will be manufactured from high quality materials such as Melamine, Polyamide…

Read More

Design of Increased Safety Equipment

Increased safety design prevents arcs, sparks and hot surfaces from occurring inside or outside the equipment. Design Features Principle and design The safe operation of Increased Safety equipment depends on the prevention of any source of ignition (excessive surface temperatures, arcs…

Read More

Equipment Protection Level (EPL): Gb

EPL Gb is the equipment protection level for equipment that is safe in normal operation and expected faults, suitable for Zone 1. Zones of Use: Increased Safety equipment may be used in Zones 1 & 2, unless a risk assessment, taking…

Read More

Increased Safety (Ex e)

Increased safety (Ex e) is an explosion protection method that prevents arcs, sparks and excessive temperatures in hazardous areas. Increased Safety (Ex e) Increased Safety Ex e concept was invented in Germany. The letter ‘e’ comes from the German phrase ‘Erhohte…

Read More

Modification of Flameproof Enclosures

Any modification of flameproof enclosures can invalidate their certification and make them unsafe. Flameproof enclosures are supplied complete with all internal components fitted and certified as a single entity by a recognised test authority. The testing procedure will take into account…

Read More

Pressure Piling

Pressure piling occurs when an explosion pre-compresses gas in another part of an enclosure, causing a much higher secondary pressure. If a flammable mixture is compressed prior to ignition, the resulting explosion pressure will be considerably higher than if the same…

Read More

Ingress Protection Methods

Ingress protection methods for flameproof equipment keep out water and dust without damaging the flamepaths. The diagrams illustrate typical locations of gaskets or rubber ‘O’ rings for ensuring a high level of ingress protection. The gasket etc. must be an integral…

Read More

Protection

Flameproof electrical protection is essential because Ex d enclosures are tested against gas explosions, not internal short circuits. Electrical Protection Flameproof enclosures are tested for their ability to withstand internal gas explosions only; they are not capable of withstanding the energy…

Read More

Fixing removable covers and fasteners

Flameproof cover fasteners must all be fitted and tight, because the enclosure’s strength depends on them. All cover fixing bolts must be fitted and fastened down “ Spanner tight” at all times, wherever the equipment could possibly be energised, even during…

Read More

Obstruction to Flamepaths

Obstruction to flamepaths can stop a flameproof joint cooling escaping gases, so minimum clearances apply. IEC / BS EN60079-14 states that the obstruction of flanged joints must be avoided, unless the equipment has been tested at smaller distances than those shown…

Read More

Entries

Flameproof entries must keep the enclosure flameproof where cables and conduits pass through its walls. Cylindrical Threads The threaded part shall be at least 8mm in length (for enclosures > 100mm3), and must have at least 5 full threads as per…

Read More

Construction

Flameproof enclosure construction relies on strong walls and narrow flamepaths that cool escaping gases. Introduction Typical materials used for the construction of flameproof equipment include cast iron and aluminium alloys. Where corrosion resistance is required, gun metal bronze, phosphor bronze and…

Read More

Principle of Operation

The flameproof principle accepts that gas may enter an enclosure and ignite, but contains the explosion safely. Flameproof enclosures are not gas tight, and a gas or vapour will enter the enclosure through joints or cable entries. Since these enclosures are…

Read More

EPL of Ex d Equipment

The Ex d EPL is normally db, which makes flameproof equipment suitable for Zones 1 and 2. Generally, Ex d equipment will have a level of protection “db” (EPL: Mb or Gb). This means that this equipment can be used in…

Read More

Flameproof (Ex d)

Flameproof protection, Ex d, contains any internal explosion so that it cannot ignite the surrounding atmosphere. Introduction to Flameproof (Ex d) Flameproof protection is one of the original methods of explosion protection developed for use in mining industry. It has a…

Read More

The IECEx Scheme

The IECEx scheme provides international certification for equipment used in explosive atmospheres. A recently introduced certification process is the IECEx scheme, which is a move towards truly global certification. However, acceptance in the EU will still require the equipment to comply…

Read More

Equipment Marking

Ex equipment marking tells you how equipment is protected and where it can be used safely. Introduction Ex Equipment is marked in accordance with the standards as illustrated below. Equipment complying with ATEX 95 will also be marked in this way,…

Read More

Product Certification

Ex product certification proves that equipment meets the standards for use in explosive atmospheres. Reasons For Product Certification The Reason for Product Certification Include: Demonstrate product quality with regard to the ability of the equipment to function safely in a hazardous…

Read More

ATEX 95 (94/9/EC), and 2014/34/EU

The ATEX directive sets the legal requirements for equipment used in explosive atmospheres in the European Union. ATEX 95 The Directive 94/9/EC (commonly known as ATEX 95, the ‘product’ directive) was adopted to enable free trade of products between EU member…

Read More

Comparison of IEC, European (CENELEC) and British Standards

This Ex standards comparison shows how IEC, CENELEC and British standards for explosion protected equipment line up. Prior to UK entry into the European Union, electrical equipment for hazardous area was manufactured to British Standard BS 4683. Equipment built and certified…

Read More

Standards, Certification and Marking

Explosion protection standards, certification and marking exist so electrical equipment can be used safely where flammable atmospheres occur. Many industries are involved in materials which can give rise to potentially explosive atmospheres by the presence of flammable mixtures of gases and/…

Read More

Table of Flammable Gases

This flammable gas table summarises the properties that decide equipment group and temperature class. Simplified data from IEC 60079-20-1 covering properties of a selection of flammable gases. Name formula Relative Density (Air=1) P Flash point (°C) Lower Flammable Limit (Vol -%)…

Read More

Mechanical Strength

Mechanical strength tests prove that Ex equipment keeps its protection after impacts and drops. Impact tests As well as having the degree of ingress protection called for in the various construction standards, enclosures for electrical equipment must pass an impact test….

Read More

Ingress Protection | IP Code

The IP code describes how well an enclosure keeps out solid objects, dust and water. Ingress Protection (IP Code) – to IEC60529 Enclosures of electrical equipment are classified according to their agility to resist the ingress of solid objects and water…

Read More

Equipment Selection

Ex equipment selection matches each item to the zone, gas group and temperature class of the location. Equipment Group In the IEC system, electrical equipment for explosive atmosphere is divided into groups. The group allocation for surface and mining industries are…

Read More

Ignition

Ignition sources include electrical sparks and arcs, hot surfaces, static electricity and mechanical friction. Sources of Ignition Sources of ignition are many and varied and include: Electrical arcs/sparks Thermite action Frictional sparks Sodium water/reaction Hot surfaces Other chemical reactions Welding Activities…

Read More

Area Classification

Area classification divides a site into zones according to how likely a flammable atmosphere is to be present. A hazardous area is defined as:‘An area in which an explosive gas atmosphere is present, or may be expected to be present, in…

Read More

Oxygen

Oxygen enrichment makes flammable atmospheres easier to ignite and more violent when they burn. Oxygen Enrichment The normal oxygen content in the atmosphere is around 20.95%. If a location has a value which exceeds this, its atmosphere is said to be…

Read More

Classification of Gases and Vapour

The classification of gases and vapours into groups and temperature classes decides which Ex equipment can be used. Gases are classified according to the group or subdivision of the equipment required for use in that particular gas, based on the gas…

Read More

Flash Point

Flash point is the lowest temperature at which a liquid gives off enough vapour to form an ignitable mixture. Flash points are normally associated with flammable materials in the liquid phase. By definition, flash point is ‘the lowest temperature at which…

Read More

Density

The relative density of gases tells you whether a released gas will rise or sink in air. It is important to know whether a flammable material will rise or fall in the atmosphere. Knowledge of where a flammable material will collect…

Read More

Fuel

Fuel characteristics such as flammable limits and ignition temperature decide how easily a release can ignite. This course covers explosives atmospheres where the fuel is gas or vapour. The International Standard for Explosive Atmosphere is IEC 60079.IEC 60079-20-1 gives data for…

Read More

Theory of combustion

The theory of combustion explains that fuel, oxygen and an ignition source must all be present for a fire or explosion. The “Triangle of Combustion” illustrates the three elements required to create an ignition or explosion. Fuel: This can be in…

Read More