The theory of combustion explains that fuel, oxygen and an ignition source must all be present for a fire or explosion. The “Triangle of Combustion” illustrates the three elements required to create an ignition or explosion. Fuel: This can be in…
Fuel
Fuel characteristics such as flammable limits and ignition temperature decide how easily a release can ignite. This course covers explosives atmospheres where the fuel is gas or vapour. The International Standard for Explosive Atmosphere is IEC 60079.IEC 60079-20-1 gives data for…
Density
The relative density of gases tells you whether a released gas will rise or sink in air. It is important to know whether a flammable material will rise or fall in the atmosphere. Knowledge of where a flammable material will collect…
Flash Point
Flash point is the lowest temperature at which a liquid gives off enough vapour to form an ignitable mixture. Flash points are normally associated with flammable materials in the liquid phase. By definition, flash point is ‘the lowest temperature at which…
Classification of Gases and Vapour
The classification of gases and vapours into groups and temperature classes decides which Ex equipment can be used. Gases are classified according to the group or subdivision of the equipment required for use in that particular gas, based on the gas…
Oxygen
Oxygen enrichment makes flammable atmospheres easier to ignite and more violent when they burn. Oxygen Enrichment The normal oxygen content in the atmosphere is around 20.95%. If a location has a value which exceeds this, its atmosphere is said to be…
Area Classification
Area classification divides a site into zones according to how likely a flammable atmosphere is to be present. A hazardous area is defined as:‘An area in which an explosive gas atmosphere is present, or may be expected to be present, in…
Ignition
Ignition sources include electrical sparks and arcs, hot surfaces, static electricity and mechanical friction. Sources of Ignition Sources of ignition are many and varied and include: Electrical arcs/sparks Thermite action Frictional sparks Sodium water/reaction Hot surfaces Other chemical reactions Welding Activities…
Equipment Selection
Ex equipment selection matches each item to the zone, gas group and temperature class of the location. Equipment Group In the IEC system, electrical equipment for explosive atmosphere is divided into groups. The group allocation for surface and mining industries are…
Ingress Protection | IP Code
The IP code describes how well an enclosure keeps out solid objects, dust and water. Ingress Protection (IP Code) – to IEC60529 Enclosures of electrical equipment are classified according to their agility to resist the ingress of solid objects and water…
Mechanical Strength
Mechanical strength tests prove that Ex equipment keeps its protection after impacts and drops. Impact tests As well as having the degree of ingress protection called for in the various construction standards, enclosures for electrical equipment must pass an impact test….
Table of Flammable Gases
This flammable gas table summarises the properties that decide equipment group and temperature class. Simplified data from IEC 60079-20-1 covering properties of a selection of flammable gases. Name formula Relative Density (Air=1) P Flash point (°C) Lower Flammable Limit (Vol -%)…