The relative density of gases tells you whether a released gas will rise or sink in air.
It is important to know whether a flammable material will rise or fall in the atmosphere.
Knowledge of where a flammable material will collect ensures that gas detectors can be located at the correct level, and that ventilation is directed accordingly.
The materials are compared with air and allocated a number to denote their relative density, given by the Greek letter ‘p’, (rho). Air has p = 1. A material with p more than 1 will fall in the atmosphere. Materials with p less than 1 will rise in the atmosphere. Typical values of density (p) of some gases are given in the table:
| Material | Relative vapour Density ‘p’ |
| Air | 1 |
| Propane | 1.56 |
| Methane | 0.55 |
| Ethylene | 0.97 |
| Hydrogen | 0.07 |
| Acetylene | 0.90 |
| Diethyl Ether | 2.55 |
| Hydrogen Sulphide | 1.19 |
| Carbon Disulphide | 2.64 |
Materials which rise in the atmosphere can collect in roof spaces.
Those which fall, such as butane or propane, can drift along at ground level and possibly into a non-hazardous location, or may collect in locations lower than ground level without ever dispersing.
Such locations should be well ventilated in order to avoid ignition due to a stray spark etc.
Using the relative density of gases #
Relative density decides where a release goes. Light gases such as hydrogen and methane rise and can collect under roofs and in ceiling voids, so detectors and vents belong at high level. Heavy vapours such as propane and petrol vapour sink and flow along the ground, collecting in pits, trenches and basements, so detectors belong near the floor.
Gases with a relative density close to 1, such as ethylene and acetylene, mix readily with air and can spread in any direction. In addition, temperature changes behaviour: a cold release of a light gas may sink at first, and a hot release of a heavy vapour may rise until it cools.
Use relative density when siting gas detectors, designing ventilation and drawing hazardous area boundaries. For more detail, read area classification and flammable gas table. Electrochlorination hydrogen, which rises quickly, is covered in our guide to hydrogen degassing. Gas data appears in IEC 60079-20-1 from IEC.