Type n equipment marking tells you which method is used to control sparks and hot surfaces in Zone 2 equipment.
The above table shows the marking on Type ‘n’ equipment to indicate the method applied to either eliminate or control spark energy and/or hot surfaces.
The following is an example “od” marking applied to type-n equipment containing sparking contacts protected by a method other than energy limitation.
Ex nC IIB T5
How to read type n marking #
Type n marking always starts with Ex n and adds a letter for the method used. A means non-sparking, C means sparking contacts protected by another method such as enclosed break or hermetic sealing, L means energy limited and R means restricted breathing. The gas group and temperature class then follow, as with other protection concepts.
Taking the example Ex nC IIB T5, the equipment contains sparking contacts that are protected by a method other than energy limitation. It is suitable for gas groups IIA and IIB, and its surface temperature stays below 100 °C, so it can be used with gases whose ignition temperature is above that.
Newer equipment may show the replacement codes instead, such as ec, dc or ic, because several type n methods have moved into other standards. Type n equipment is limited to EPL Gc, which normally means Zone 2. For context, read type n equipment variations and Ex equipment marking. Marking rules are harmonised through the IECEx scheme.