Type n protection is a cost-effective explosion protection concept for equipment used in Zone 2. Definition Type ‘n’ protection is a type of protection applied to electrical equipment such that in normal operations and in certain specified regular expected occurrences, it…
Principle and Design
Type n design prevents ignition sources in normal operation using features similar to increased safety equipment. Type ‘n’ protection is similar in concept to increased safety type ‘e’ protection, and the design features ensure that, in normal operation, sources of ignition…
Additional Protection Measures
Type n additional protection measures allow sparking or hot components to be used safely in Zone 2 equipment. Additional protection measures The additional protection measures included for components which produce arcs/sparks or hot surfaces are explained below: Energy limited equipment and…
Marking
Type n equipment marking tells you which method is used to control sparks and hot surfaces in Zone 2 equipment. The above table shows the marking on Type ‘n’ equipment to indicate the method applied to either eliminate or control spark…
Cable Glands
Type n cable glands must be certified and, for Ex nR equipment, maintain the enclosure’s restricted breathing. Ex ‘n’ gland certification etc. According to IEC60079-14, cable glands for Ex n (and for Ex e) must be certified as meeting the requirements…
Summary of Type ‘n’ Equipment Variations
This summary of type n equipment variations shows how nA, nC, nL and nR relate to newer protection codes. This table summarises the variations in Type ‘n’ Equipment Type ‘n’ equipment variation Marking Energy limited equipment “nL” replaced by ‘ic’ Protected…