Type n cable glands must be certified and, for Ex nR equipment, maintain the enclosure’s restricted breathing.
Ex ‘n’ gland certification etc.
According to IEC60079-14, cable glands for Ex n (and for Ex e) must be certified as meeting the requirements of IEC60079-0.
Glands certified Ex e are suitable for Ex n use under the new standards.
Before 2007, it was only required that the impact and IP ratings for the type of protection were met, and some uncertified glands could fulfil these criteria.
Ex nR installation, and cable entries
You must consult the particular Ex nR equipment installation instruction
Gland entries on some Ex nR equipment require the use of special sealing arrangements. If so, restricted breathing seals or washers will be provided by the equipment manufacturer. The documentation will indicate if restricted breathing seals are required, or if normal IP seals may be used.
To maintain the restricted breathing properties of Ex nR equipment via the actual cable glands, certified Ex d / Ex e / Ex nR glands are now available, and should be used where applicable.
Installing type n cable glands correctly #
The cable gland is part of the enclosure’s protection, so the wrong gland can undo a good installation. Under current rules, glands used with type n equipment must be certified to IEC 60079-0. In practice, glands certified for increased safety are widely used because they meet the same requirements.
Restricted breathing equipment, Ex nR, needs extra care. Its enclosure is designed to limit how quickly gas can enter, so every entry must keep that seal. The equipment documentation states whether special restricted breathing seals are required, and the manufacturer usually supplies them. Where available, glands certified for Ex nR, as well as Ex d and Ex e, provide the simplest solution.
After installation, check that unused entries are closed with certified stopping plugs and that glands are tightened correctly. For general guidance, read Ex cable glands and type n protection. Gland certification is covered by the IECEx scheme.