Purging removes any flammable gas from a pressurised enclosure before its electrical equipment is energised.
Purging involves passing a specified quantity of the safe gas through the enclosure in order to remove any flammable gases which may have entered. The standards specify that the minimum volume of the safe gas required to achieve adequate purging is equivalent to 5 times the internal volume of the enclosure and associated ducting. Manufacturers may, however, recommend a greater number of air changes.
Depending on the pressurisation type the purge duration may be controlled manually, or automatically via a flow-rate sensor and timer. If there is a purge failure or loss of pressure the control system must automatically reset and the purge cycle be started again. Very large systems require on site tests to establish the purge duration necessary.
Getting purging right #
Purging is the step that makes it safe to switch on. Before power is applied, any flammable gas that leaked in while the system was off must be flushed out. The minimum is five times the free volume of the enclosure and its ducts, although manufacturers often specify more for complex enclosures with dead spaces.
The purge must be proven, not assumed. A flow monitor at the outlet confirms that protective gas is moving, and a timer ensures the full volume has passed before the control system enables power. If flow or pressure drops during purging, the sequence must reset and start again from the beginning.
For very large enclosures, such as pressurised rooms, site tests confirm the purge time needed, because calculations alone may miss stagnant areas. For related topics, read pressurisation safety devices and protective gas. Purge requirements are defined in IEC 60079-2, published by IEC.