The required action on loss of pressure depends on the zone and on what equipment is inside the pressurised enclosure.
No internal source of release #
The over-pressure within the enclosure is monitored by a pressure switch/sensor, and a flow-rate switch/sensor, located at the exhaust duct, is used to monitor the rate of flow of the safe gas through the enclosure. Loss of over-pressure or rate of flow will activate either an alarm or shutdown of the internal electrical components, the action taken being dependent on:
- The EPL requirement of the area in which the system is located;
- The type of equipment/components within the enclosure.
IEC 60079-14:2013, Table 18, specifies the action to be taken on loss of pressure as follows:
| EPL requirement | Enclosure contains equipment not meeting EPL ‘Gc’ requirements without pressurisation | Enclosure contains equipment meeting EPL ‘Gc’ requirements without pressurisation |
| ‘Gb’ | Alarm and switch off a | Alarm b |
| ‘Gc’ | Alarm b | No action |
a – If automatic switch-off would introduce a more dangerous condition, other precautionary measures should be taken, for example, duplication of protective gas supply.
b – If the alarm operates, immediate action should be taken to restore the integrity of the system.
With an internal source of release #
The action to be taken depends on the Zone, type of equipment and the type/severity of the release. (Details are beyond the scope of these notes).
Planning the response to loss of pressure #
Loss of pressure means that flammable gas could enter the enclosure. The required response depends on two questions: what EPL the location needs, and whether the equipment inside would be safe on its own in Zone 2. In a Gb location with ordinary equipment inside, the system must alarm and switch off. Where the internal equipment already meets Gc, an alarm is enough.
Switching off is not always the safest choice. If shutting down would create a greater hazard, for example by stopping a critical process, other measures can be used, such as a duplicate protective gas supply. In every case, operators must respond to an alarm promptly and restore pressure.
Document the agreed action for each enclosure and test it during commissioning and inspection. For the devices that detect loss of pressure, read pressurisation safety devices and types of pressurisation. The rules appear in IEC 60079-14, published by IEC.