Increased safety (Ex e) is an explosion protection method that prevents arcs, sparks and excessive temperatures in hazardous areas.
Increased Safety (Ex e) #
Increased Safety Ex e concept was invented in Germany. The letter ‘e’ comes from the German phrase ‘Erhohte Sicherheit’ which means ‘increased security’.
This method of protection has been widely used for many years and has a good safety record, comparable with the other methods of protection.
Typical applications are induction motors, lighting fittings and junction boxes.

Standards #
| Current constructional standards | |
| IEC 60079-7: 2015 BS EN60079-7: 2007 | Equipment protection by increased safety “e” |
| Codes of Practice | |
| IEC 60079-14: 2013 BS EN60079-14: 2014 | Explosive atmospheres: Part 14 Electrical installations design, selection & erection |
| IEC 60079-17: 2013 BS EN60079-17: 2014 | Explosive atmospheres: Part 17 Electrical installation inspection and maintenance |
Definition #
‘A type of protection applied to electrical apparatus in which additional measures are taken to give increased security against the possibility of excessive temperatures, and of the occurrence of arcs and sparks in normal service or under specified fault conditions’.
Specified fault conditions include foreseeable abnormal operation such as motor overload or lamp failure.
Where increased safety is used #
Increased safety is one of the most widely used protection methods because it keeps equipment simple. Junction boxes, terminal boxes, induction motors and light fittings are the classic applications. Without heavy flameproof walls, enclosures are lighter, easier to open and simpler to wire.
The trade-off is that increased safety equipment must not contain anything that sparks in normal operation. Switches, contactors and other sparking parts therefore need another method, which is why many products combine Ex e with flameproof or encapsulated components. In addition, motors need protection relays matched to their tE time.
Today, increased safety covers two levels: eb for EPL Gb and ec for EPL Gc, the latter replacing the old type nA. For more detail, read increased safety design, Ex e motors and increased safety terminals. AZUVIA certifications include increased safety equipment certified under the IECEx scheme.