Surge suppression protects intrinsically safe instrument loops from transients caused by power faults and lightning.
Electronic equipment and instrumentation are always at risk from surges and transients caused by power faults or nearby lightning strikes. Surge suppression devices (transient voltage suppressors or TVS’s) are often fitted close (within one metre) to the parts of the loop requiring protection.
Surge devices may be classed as simple equipment if they are not energy storing or energy generating. Examples include TVS’s incorporating gas discharge tubes, voltage dependent resistors, and diodes.
Applying surge suppression to IS loops #
Instrument loops run long distances across plants, so they pick up surges from lightning and power faults. A surge can damage barriers and field devices, and in the worst case it can defeat the energy limitation that makes the loop safe. Surge suppression diverts that energy to earth before it reaches sensitive equipment.
Devices are usually fitted at both ends of the loop: one near the field device, typically within about a metre, and one in the safe area near the barrier or isolator. Because surge devices connect to earth, the earthing design must be considered carefully, especially where the IS system relies on a single earth point.
Many surge suppressors qualify as simple apparatus, because they neither store nor generate energy. Even so, their capacitance and inductance should be included in the loop calculation. For more detail, read IS parameters and zener barrier. Lightning protection practice is covered by IEC standards.