The oil immersion principle keeps sparking and hot parts under a protective liquid so flammable gas cannot reach them.
The oil level in the equipment is used to completely cover components which arc/spark or produce hot surfaces during normal operation, establishing a barrier between these components and any flammable gases which may be present above the oil or outside the enclosure.
In this method of protection, cooling is aided by circulation of the oil (by convection), dispersing the heat produced in hot-spots.
The oil quenches arcs occurring at switching contacts. Where mineral oil is used, these arcs will produce hydrogen and acetylene as by-products.
In the UK this condition was considered to be undesirable and, until recently, Ex ‘o’ was limited to Zone 2. Later standards have stricter specifications, and this type of protection is now permitted in Zone 1. They allow for the use of unused mineral oil to IEC 60296 for the protective liquid, as well as other types such as silicone insulating liquids having specified properties.
Maintaining equipment that uses the oil immersion principle #
The oil immersion principle only works while the liquid covers every ignition source. Therefore, the most important check is the liquid level. Equipment is fitted with a level indicator, and the level must stay within the marked limits across the operating temperature range, because oil expands as it warms.
Oil quality matters too. Arcing breaks down mineral oil, producing hydrogen and acetylene, and moisture reduces its insulating strength. Periodic sampling, filtration or replacement keeps the liquid within specification. In addition, any pressure relief device and breather must be clear, and the enclosure must not leak.
Newer editions of the standard permit Ex o in Zone 1, using new mineral oil to IEC 60296 or other specified liquids such as silicone. For more detail, read oil immersion construction and Ex o oil immersion. AZUVIA’s oil-immersed rectifiers use a related design for harsh duty. The standards are published by IEC.