The powder filling principle relies on fine granules to stop a flame from spreading out of Ex q equipment.
The filling, which may be quartz or glass particles, achieves safety by what is known as “suppression of flame propagation”. The flammable gas or vapour may permeate the granules and reach the parts producing arcs/sparks or hot surfaces, but the quantity of gas will be too small to support an explosion within the inert powder.
Tests specified in the construction standard provide a safe correlation between the depth of granules and the duration & level of the arc current produced by the components.
This method of protection is suitable for use in all group II gases or vapours.
Why the powder filling principle works #
An explosion needs a flame to spread from its source into the surrounding gas. In powder-filled equipment, the parts that can spark or run hot are buried in fine quartz or glass granules. Gas may seep between the grains, but the spaces are so small that a flame cannot travel through them. The heat is absorbed by the granules, and the flame dies out before it reaches the surface.
Because the protection relies on depth of filling, tests in the standard link the depth of granules to the energy and duration of any arc. That is why powder filling is common for capacitors and ballasts, which can fail with short arcs, rather than for heavy switching devices.
The method is suitable for all Group II gas subdivisions, IIA, IIB and IIC, and is normally used in Zones 1 and 2. It is often combined with other methods, for example in Ex deq light fittings. Read powder filling construction and Ex deq light fittings to learn more. The relevant standard, IEC 60079-5, is published by IEC.