title: Jointing of Cables
description: Jointing of cables in hazardous areas should be avoided where possible and, when needed, must keep the installation safe. In hazardous areas, wherever possible, cable runs should be continuous and without interruption. Where discontinuity cannot be avoided, the joint, in…
url: "https://www.azuvia.co/kb/wiring-systems-installation/jointing-of-cables/"
updated: "2026-11-07"
category: "Explosion Proof Basics / Wiring Systems & Installation"
---

# Jointing of Cables

Jointing of cables in hazardous areas should be avoided where possible and, when needed, must keep the installation safe.

In hazardous areas, wherever possible, cable runs should be continuous and without interruption. Where discontinuity cannot be avoided, the joint, in addition to being mechanically, electrically and environmentally suitable for the situation shall be made by

- An enclosure having a type of explosion protection suitable for the Zone**or**
- Using epoxy or compound filled cable jointing kit **or**
- Using heat shrink sleeving in accordance with the manufacturers instructions.

Whichever method is used, the joints must be mechanically, electrically and environmentally appropriate. Conductor connections are required to be made by:

- Compression connectors, **or**
- Secured screw connectors, **or**
- Welding or brazing.
- Soldering is permissible if the conductors being connected are held together by suitable mechanical means whilst being soldered.

The above points are taken from the IEC 60079:2007. They are not covered in the 2013 edition, but are expected to be reinstated in later editions.

## Good practice for jointing of cables

The best joint is no joint. Every joint is a potential weak point for mechanical damage, moisture and poor connections, so cable runs in hazardous areas should be continuous wherever possible. When a joint is unavoidable, for example after damage or to extend a circuit, it must be made in a way that keeps the installation suitable for the zone.

There are three accepted methods: an enclosure with a suitable type of protection, a resin or compound-filled jointing kit, or heat-shrink sleeving applied to the manufacturer's instructions. Conductors are then joined by compression connectors, secured screw connectors, welding or brazing. Soldering alone is not enough; the conductors must also be held mechanically.

Record every joint on the installation drawings so inspectors know where it is. For related topics, read [hazardous area cables](/kb/wiring-systems-installation/basics-on-cables-wiring-system-installation/) and [hazardous area installation requirements](/kb/wiring-systems-installation/other-installation-requirements/). The installation rules themselves come from IEC 60079-14, published by [IEC](https://www.iec.ch/).