# Type ‘n’ Protection

Type n protection is a cost-effective explosion protection concept for equipment used in Zone 2.

## Definition

Type ‘n’ protection is a type of protection applied to electrical equipment such that in normal operations and in certain specified regular expected occurrences, it is not capable of igniting a surrounding flammable gas atmosphere.

Type **‘N’**, a UK innovation, became an accepted method of explosion protection in Europe as type ‘n’ to EN50021. Type ‘n’ is now accepted internationally to IEC60079-15.

## Equipment Protection Level (EPL): Gc

Type ‘n’ equipment is basically similar to increased safety type ‘e’ equipment, but that there is a relaxation in the constructional requirements because it can only be used where the required EPL is Gc. Generally, this means locations in Zone 2 only, unless a risk assessment indicates differently.

## Standards

| **Current constructional standards** |  |
| --- | --- |
| IEC 60079-15: 2010 BS EN 60079-15: 2010 | Explosive atmospheres – Part 15: Equipment protection by type of protection ‘n’ |
| **Original standard** |  |
| BS 6941: 1988 | Electrical equipment for explosive atmospheres with type of protection N |
| **Codes of Practice** |  |
| IEC 60079-14: 2013 BS EN60079-14: 2014 | Electrical Equipment for explosive gas atmospheres: Part 14 Electrical installations in hazardous areas (other than mines) |
| IEC 60079-17: 2013 BS EN60079-17: 2014 | Electrical Equipment for explosive gas atmospheres: Part 17 Inspection and Maintenance of electrical installations in hazardous areas (other than mines) |

## Ambient Conditions:

Unless otherwise marked, type ‘n’ enclosures are designed for use in ambient temperatures in the range -20°C to +40°C.

## IP Rating

The minimum IP rating for Ex n equipment containing bare live parts is IP54. For enclosures with no bare live parts IP44 is sufficient.

## When type n protection is the right choice

Type n protection is designed for Zone 2, where a flammable atmosphere is not expected in normal operation and, if it occurs, lasts only a short time. Because the risk is lower, the construction rules are relaxed compared with Zone 1 methods. As a result, type n equipment is often lighter and less expensive, which makes it attractive for large areas classified as Zone 2.

However, it must never be used in Zone 1 or Zone 0, unless a risk assessment specifically allows it. Always check the area classification drawing first. In addition, check the ambient range: unless marked otherwise, type n equipment is designed for minus 20 °C to plus 40 °C, which may not suit very hot or cold sites.

Several type n methods have moved into other standards, so newer equipment may carry codes such as ec or ic instead. For details, read [type n design](/kb/type-n-equipment/basics-on-type-n-design/) and [type n equipment variations](/kb/type-n-equipment/basics-on-type-n-equipment-summary/). Equipment of this type is certified through the [IECEx scheme](https://www.iecex.com/).