# Principle and Design

Type n design prevents ignition sources in normal operation using features similar to increased safety equipment.

Type ‘n’ protection is similar in concept to increased safety type ‘e’ protection, and the design features ensure that, in normal operation, sources of ignition in the form of excessive surface temperatures, arcs or sparks are prevented from occurring either internally or externally.

Since the design requirements are not as strict as those for increased safety type ‘e’, it is possible for the manufacturer to install components which produce hot surfaces, arcs or sparks, providing these components incorporate additional methods of protection. These additional methods are described later in this unit.

The principal design features for type ‘n’ are:

1. Enclosures, protective covers, motor fan guards and cable glands are required to be impact tested to standards, according to whether the risk of impact is high or low.
   Equipment for low impact areas will have a certificate with suffix ‘X’
2. Minimum ingress protection IP54 where an enclosure has exposed live parts internally, or IP44 where insulated live parts are used internally
3. Use of certified terminals
4. Terminals manufactured from high quality insulation material
5. Specified creepage and clearance distances incorporated into the design of the terminals
6. Terminal locking devices to ensure conductors remain secure in service.

![](https://www.azuvia.co/wp-content/uploads/2026/11/type-n-protection-design.png)

## Type n design compared with increased safety

Type n design follows the same idea as increased safety: prevent sparks and hot surfaces in normal operation. The difference is the level of assurance. Because type n is only for Zone 2, where a flammable atmosphere is unlikely and short-lived, the design need not consider faults in the same depth, so equipment can be simpler and cheaper.

Even so, the core features matter. Enclosures pass impact tests appropriate to the risk of damage, IP ratings keep out dust and water, and certified terminals with suitable creepage and clearance distances keep connections cool and secure. Where a component does spark or run hot, one of the additional protection measures is applied.

For users, the key is to install type n equipment only where EPL Gc is permitted, and to keep its seals, glands and terminals in good order. For more detail, read [type n additional protection](/kb/type-n-equipment/basics-on-type-n-additional-protection-measures/) and [increased safety design](/kb/increased-safety-ex-e/basics-on-increased-safety-design/). The standard, IEC 60079-15, is published by [IEC](https://www.iec.ch/).