description: "Equipment energised without overpressure must have its own explosion protection because pressurisation no longer protects it. An anti-condensation heater may be used in a rotating electrical machine to prevent internal surfaces and atmosphere becoming cold, thereby preventing the formation of…"
url: "https://www.azuvia.co/kb/pressurisation-ex-p/basics-on-equipment-energised-during-absence-of-overpressure/"
updated: "2026-11-07"
category: Explosion Proof Basics / Pressurisation (Ex p)
---

# Equipment Energised During Absence of Overpressure

Equipment energised without overpressure must have its own explosion protection because pressurisation no longer protects it.

An anti-condensation heater may be used in a rotating electrical machine to prevent internal surfaces and atmosphere becoming cold, thereby preventing the formation of moisture in the windings. Because the heater will be energised when the machine is without over-pressure, it is essential that it is explosion protected.

Emergency lighting will normally be installed in pressurised control rooms, cabins etc. and energised when there is loss of over-pressure. These fittings must also be explosion protected, typically Ex e. Solenoids for fire dampers will be Ex d protected. Alarms, over-pressure and flow-rate sensors may use IS protection. Ex d enclosures will be used for control panels.

![](https://www.azuvia.co/wp-content/uploads/2026/11/Equipment-Energized-During-Absence-of-Overpressure.png)

## Protecting equipment energised without overpressure

Pressurisation protects the inside of an enclosure only while protective gas holds it above outside pressure. Some equipment, however, must keep working when that pressure is lost. Anti-condensation heaters keep motor windings dry when the motor stops, and emergency lighting must come on when the main supply or ventilation fails.

Each of these items needs its own explosion protection suitable for the zone. Typically, heaters and lights use increased safety or flameproof construction, fire damper solenoids use flameproof protection, and alarm and pressure sensors often use intrinsic safety. Control panels that must remain live are housed in flameproof enclosures.

Identify these items early in design, list them in the documentation and label them on site so maintenance staff know they may be live. For related guidance, read [Ex pde hybrid protection](/kb/combined-hybrid-methods-of-protection/basics-on-ex-pde/) and [loss of pressure](/kb/pressurisation-ex-p/basics-on-action-on-pressure-loss/). Equipment of this type is certified through the [IECEx scheme](https://www.iecex.com/).