# Controls & Safety Devices

Pressurisation safety devices monitor overpressure and flow so the enclosure is only energised when it is safe.

The level of overpressure will be monitored by a pressure sensor or switch located in the enclosure,
at the most difficult point at which to maintain overpressure.

The rate of flow through the enclosure will be monitored by a flow-rate sensor or switch. A pressure gauge is also desirable and should be located where it can be easily read.

When the safe gas is provided from a compressed-air system or cylinders a pressure relief valve should be installed in case of failure of the regulator.

Typical pressurisation monitoring etc.

1. Over-pressure monitoring device
2. Protective gas flow-rate monitoring Device.
3. Pressure gauge
4. Pressure relief valve: setting 75% of maximum declared safe over-pressure

![typical presurisation monitoring](https://www.azuvia.co/wp-content/uploads/2026/11/controls-and-safety-devices.png)

![](https://www.azuvia.co/wp-content/uploads/2026/11/pressurisation-control-system.png)

## Pressurisation Control Systems – marking

A purge and pressurisation control system with a separate certificate is marked as**associated equipment.**

- If the control system is for use in the hazardous area, the marking is: **Ex [p]**

- If the control system is for use in a non-hazardous area, marking is: **[Ex p]**

## Setting up pressurisation safety devices

Pressurisation safety devices are what make an Ex p system trustworthy. The pressure monitor must sit at the point where pressure is hardest to maintain, often far from the inlet. The flow monitor normally sits at the outlet, so it proves that protective gas is actually passing through the enclosure rather than leaking elsewhere.

The control sequence is equally important. Power must stay off until purging is complete, then the system must keep monitoring and act on any loss of pressure or flow. Purge timers, interlocks and relays are therefore part of the safety function and should be certified as part of the control system.

Test these devices during commissioning and periodic inspection, and record the set points. A relief valve set at about 75 percent of the maximum safe overpressure protects against regulator failure on compressed air supplies. For related topics, read [purging](/kb/pressurisation-ex-p/basics-on-purging/) and [loss of pressure](/kb/pressurisation-ex-p/basics-on-action-on-pressure-loss/). Control systems are certified through the [IECEx scheme](https://www.iecex.com/).