# Oil-immersion Ex o / EEx o

Ex o oil immersion protection is used mainly for heavy-duty transformers and switchgear in hazardous areas.

Oil-immersion is typically used for heavy duty transformers and switchgears.

## Standards

| Current constructional standards |  |
| --- | --- |
| IEC 60079-6: 2007 BS EN60079-6: 2007 | Explosive Atmospheres – Part 6: Equipment Protection by Oil Immersion, “o” |
| Older standards |  |
| BS EN50015: 2005 | Oil immersion ‘o’ |
| BS 5501-2: 1977 | Oil immersion ‘o’ |
| Codes of Practice |  |
| BS 5354: Part 9: 1979 (Withdrawn) | Installation and maintenance requirements for electrical equipment with type of protection ‘o’ oil-immersed equipment |

**Note:**

Since IEC/EN60079-14 and IEC/EN60079-17 do not provide selection, installation, inspection and maintenance requirements for oil-immersed equipment, BS 5345: Part 9 remains a useful reference for guidance, for the UK.

Oil immersed, equipment shall be installed in accordance with manufacturer’s documentation.

It is expected that installation details for oil filled equipment will be included in the next edition.

## Definition

The definition for this type of protection is:

‘A type of protection in which the electrical equipment or parts of the electrical equipment are immersed in protective liquid in such a way that an explosive gas atmosphere which may be above the liquid or outside the enclosure, cannot be ignited.’

## Zones of Use : 1& 2

## Levels of protection : Ex “ob” and Ex “oc”

![oil immersion ex o / eex o](https://www.azuvia.co/wp-content/uploads/2026/11/Ex-o.png)

## Where Ex o oil immersion is used

Ex o oil immersion suits heavy electrical equipment that already uses insulating oil, such as transformers, switchgear and large resistors. Because the oil also cools the components, it suits high power ratings. However, the method is not suited to portable equipment or to equipment that may be tilted, because the oil level must stay above every ignition source.

The current standard defines two levels of protection. Level ob is for EPL Gb, normally Zones 1 and 2, while level oc is for EPL Gc and Zone 2 only. Installation must follow the manufacturer's documentation, including mounting level, liquid filling and any monitoring devices.

During inspection, check the liquid level, look for leaks and confirm that breathers and relief devices are in good order. For background, read [oil immersion principle](/kb/oil-immersion-ex-o-eex-o-ex/basics-on-oil-immersion-principle/) and [oil immersion construction](/kb/oil-immersion-ex-o-eex-o-ex/basics-on-oil-emersion-construction/). Related equipment is certified through the [IECEx scheme](https://www.iecex.com/).