description: "A typical IS system layout links safe-area equipment to field devices through an energy-limiting interface. ![typical layout of I.S system](https://www.azuvia.co/wp-content/uploads/2026/11/typical-layout-of-I.S-system.png) An IS system usually consists of safe area equipment, a safe to hazardous area interface, cables and junction boxes, and…"
url: "https://www.azuvia.co/kb/intrinsic-safety-ex-i/basics-on-typical-layout-of-i-s-system/"
updated: "2026-11-07"
category: Explosion Proof Basics / Intrinsic Safety (Ex i)
---

# Typical I.S. system layout

A typical IS system layout links safe-area equipment to field devices through an energy-limiting interface.

![typical layout of I.S system](https://www.azuvia.co/wp-content/uploads/2026/11/typical-layout-of-I.S-system.png)

An IS system usually consists of safe area equipment, a safe to hazardous area interface, cables and junction boxes, and field (hazardous area) equipment. The system is designed to guard against the possibility of particular faults occurring.

**The intrinsic safety concept applies to the whole system and not to any one item only.**

#### **Associated apparatus (interface)**

The equipment in the safe area is connected to equipment in the hazardous area via the interface, which is the **associated apparatus.**

The **function of the interface** is to **limit the energy** into the hazardous area and is often called the **I.S. Safety Barrier.**

There are two types of I.S barriers:

- Zener barrier
- Galvanic isolation barrier

The interface may be incorporated inside the safe area apparatus (e.g. a recorder with an energy-limited input from a sensor in the hazardous area).

## Planning an IS system layout

Good IS system layout starts at the design stage. Each loop should be documented with a descriptive system document or loop diagram showing the field device, cables, junction boxes and the barrier or isolator, together with their parameters. This document is what inspectors check against, so keep it current.

Segregation is the next priority. IS circuits must be kept apart from non-IS circuits in cable trays, junction boxes and cabinets, either by distance or by barriers. In addition, IS terminals are usually coloured light blue, and IS cables are often identified the same way, which helps prevent accidental connection to other circuits.

Finally, decide between zener barriers and galvanic isolators, because this choice affects earthing. For each option, read [zener barrier](/kb/intrinsic-safety-ex-i/basics-on-zener-barrier/) and [galvanically isolated barriers](/kb/intrinsic-safety-ex-i/basics-on-galvanic-isolation/), then see [installation of IS equipment](/kb/intrinsic-safety-ex-i/basics-on-installation-of-is-equipment/). The rules come from IEC 60079-11 and 60079-14, published by [IEC](https://www.iec.ch/).