title: Marking
description: "Intrinsic safety marking shows whether equipment is field apparatus or associated apparatus, and its level of protection. **Associated apparatus not suitable for installation in a hazardous area** will be certified and marked with the Ex symbol and the type of…"
url: "https://www.azuvia.co/kb/intrinsic-safety-ex-i/basics-on-intrinsic-safety/"
updated: "2026-11-07"
category: Explosion Proof Basics / Intrinsic Safety (Ex i)
---

# Marking

Intrinsic safety marking shows whether equipment is field apparatus or associated apparatus, and its level of protection.

**Associated apparatus not suitable for installation in a hazardous area** will be certified and marked with the Ex symbol and the type of protection, all within the same square brackets:

**e.g. [Ex ia] IIC**

For **associated apparatus suitable for installation in a hazardous area,** and where the energy limitation is provided inside the equipment in the hazardous area, the symbols of the type of protection are enclosed within square brackets:

**e.g. Ex d [ib] IIC T5 or Ex px [ia] IIB T4**

This marking would mean: **the enclosure is flameproof and contains associated ‘intrinsically safe’ equipment.**

**Certified intrinsically safe field equipment**, for mounting in the hazardous area, will be **marked** with the type of protection in the normal way:

**e.g. Ex ia IIC T6 Ex ib IIC T5 Ex ic IIB T4**

**Simple Apparatus** is not required to be marked.

## Reading intrinsic safety marking

The square brackets are the key to intrinsic safety marking. Brackets around the whole Ex marking, such as [Ex ia] IIC, mean associated apparatus that must be installed in the safe area. Brackets around only the IS part, such as Ex d [ib] IIC T5, mean the apparatus may sit in the hazardous area because another method protects it. No brackets, such as Ex ia IIC T6, means field equipment for the hazardous area.

Next, read the level and group. The letters ia, ib or ic show the level of protection, and the gas group IIA, IIB or IIC shows which gases the circuit is safe for. Field devices also carry a temperature class. Simple apparatus, such as switches and thermocouples, does not need marking, although it must still be assessed.

Finally, compare the parameters of every item in the loop. Read [IS parameters](/kb/intrinsic-safety-ex-i/basics-on-intrinsically-safe-parameter/) and [intrinsic safety levels of protection](/kb/intrinsic-safety-ex-i/basics-on-level-of-protection-intrinsic-safety/) for the next steps. Marking rules are harmonised through the [IECEx scheme](https://www.iecex.com/).