title: Galvanically Isolated Barriers
description: "Galvanically isolated barriers limit energy into the hazardous area without a direct electrical connection to the safe area. ## Galvanically Isolated Barriers Devices which overcome the limitations of zener barrier are called **isolation** interfaces. Typically, the isolation required may be…"
url: "https://www.azuvia.co/kb/intrinsic-safety-ex-i/basics-on-galvanic-isolation/"
updated: "2026-11-07"
category: Explosion Proof Basics / Intrinsic Safety (Ex i)
---

# Galvanically Isolated Barriers

Galvanically isolated barriers limit energy into the hazardous area without a direct electrical connection to the safe area.

## Galvanically Isolated Barriers

Devices which overcome the limitations of zener barrier are called **isolation** interfaces.

Typically, the isolation required may be achieved by using transformers, opto-couplers and/or relays.

These **galvanically isolated barriers** are barriers which allow transference of energy from one side to the other, **without any direct wired connection** between the power source on the one side and the hazardous area terminals on the other.

The galvanic isolator must prevent high voltage break-through into the hazardous area, and limit the voltage and current to the hazardous area.

## Examples of Galvanic Isolation

In this example, isolation between the hazardous and safe areas is achieved by means of a high integrity transformer and relay.*The voltage & current limiting circuitry is not shown.*

![galvanic isolation](https://www.azuvia.co/wp-content/uploads/2026/11/galvanic-isolation-example.png)

## Opto-coupler isolation

In an opto-isolator, light or infrared emitted from the LED falls onto the phototransistor, transmitting the signal from hazardous to safe area.

![opto coupler isolation](https://www.azuvia.co/wp-content/uploads/2026/11/opto-coupler-isolation-2.png)

Note that the galvanic isolator incorporates a resistor/zener circuit to do the actual energy limiting, in the same way as in a discrete zener barrier.

Many types of galvanic isolator are available to meet specific instrumentation requirements.

![opto coupler isolation 2](https://www.azuvia.co/wp-content/uploads/2026/11/opto-coupler-isolation-2.png)

## Earthing of Galvanic units

The major advantage of **galvanic isolation barrier** that an **intrinsically safe earth is not required**.

They can be used in earth-free instrumentations (where a single earth fault would not cause a hazard) or where the hazardous area measuring device is earthed via the plant.

## Choosing galvanically isolated barriers

Galvanically isolated barriers have largely replaced zener barriers in new plants. Their main advantage is that they do not need a dedicated, high-integrity IS earth, which is difficult and costly to provide on many sites. They also tolerate earth faults in the field wiring better and can provide extra functions, such as signal conversion and alarms.

However, they are more complex and usually more expensive per channel, and they need their own power supply. When selecting an isolator, check that its output parameters suit the field device, its gas group matches the hazard, and its function suits the signal type, such as 4 to 20 mA input, digital input or valve output.

As always, the whole loop must be verified with the entity parameters. Read [zener barrier](/kb/intrinsic-safety-ex-i/basics-on-zener-barrier/) to compare the two approaches, and [IS parameters](/kb/intrinsic-safety-ex-i/basics-on-intrinsically-safe-parameter/) for the calculation. Isolators for hazardous areas are certified through the [IECEx scheme](https://www.iecex.com/).