# Table of Flammable Gases

This flammable gas table summarises the properties that decide equipment group and temperature class.

**Simplified data from IEC 60079-20-1 covering properties of a selection of flammable gases.**

| **Name formula** | **Relative Density (Air=1)** **P** | **Flash point (°C)** | **Lower Flammable Limit (Vol -%)** | **Upper Flammable Limit (Vol -%)** | **Auto Ignition Temperature (°C)** | **MESG (mm)** | **MIC ratio** | **Temperature class** | **Equipment Group** |
| --- | --- | --- | --- | --- | --- | --- | --- | --- | --- |
| **Acetone** | **2.0** | **-20** | **2.5** | **14.3 at 100C°** | **539** | **1.01** | **1.0** | **T1** | **IIA** |
| **Acetylene** | **0.90** | **Gas** | **2.3** | **100** | **305** | **0.37** | **0.28** | **T2** | **IIC** |
| **Benzaldehyde** | **3.66** | **64** | **1.4** | **–** | **192** | **–** | **–** | **T4** | **IIA** |
| **Benzene** | **2.7** | **-11** | **1.2** | **8.6** | **498** | **0.99** | **1.00** | **T1** | **IIA** |
| **Carbon Disulphide** | **2.64** | **-30** | **0.6** | **60** | **90** | **0.34** | **0.39** | **T6** | **IIC** |
| **Cyclohexane** | **2.83** | **-17** | **1.0** | **8.0** | **244** | **0.94** | **–** | **T3** | **IIA** |
| **Diethyl Ether** | **2.55** | **-45** | **1.7** | **39.2** | **175** | **0.87** | **0.88** | **T4** | **IIB** |
| **Ethylene** | **0.97** | **Gas** | **2.3** | **36** | **440** | **0.65** | **0.63** | **T2** | **IIB** |
| **Gasoline** | **3** | **-46** | **1.4** | **7.6** | **280** | **–** | **–** | **T3** | **–** |
| **Hydrogen** | **0.07** | **Gas** | **4.0** | **77** | **560** | **0.29** | **0.25** | **T1** | **IIC** |
| **Hydrogen Sulphide** | **1.19** | **Gas** | **4.0** | **45.5** | **260** | **0.83** | **–** | **T3** | **IIB** |
| **Kerosene** | **–** | **38 to 72** | **0.7** | **5.0** | **210** | **–** | **–** | **T3** | **IIA** |
| **Methane (fire damp)** | **0.55** | **Gas** | **4.4** | **17** | **595** | **1.14** | **–** | **T1** | **I** |
| **Methanol** | **1.11** | **8.0** | **6.0** | **36 at 60** **C** **50 at 100** **C** | **440** | **0.92** | **0.82** | **T2** | **IIA** |
| **Propane** | **1.56** | **Gas** | **1.7** | **10.9** | **450** | **0.92** | **0.82** | **T2** | **IIA** |

## How to use the flammable gas table

This flammable gas table brings together the properties that decide equipment selection. The gas group, IIA, IIB or IIC, comes from MESG and MIC ratio and tells you which group of equipment is needed. The auto-ignition temperature sets the temperature class, while relative density shows whether a release will rise or sink.

For example, hydrogen is group IIC with a high ignition temperature, so equipment must be IIC but can be T1. Carbon disulphide is also IIC but ignites at only 90 °C, so it needs T6 equipment. Propane is IIA and heavier than air, so it collects at low level, where gas detectors should be placed.

The table is simplified; always use the full data in IEC 60079-20-1 for design. For more detail, read [classification of gases](/kb/general-principles/classification-gases-vapour/), [relative density of gases](/kb/general-principles/gaseous-fuel-density/) and [flash point](/kb/general-principles/flash-point/). The data standard is published by [IEC](https://www.iec.ch/).