title: Flash Point
description: Flash point is the lowest temperature at which a liquid gives off enough vapour to form an ignitable mixture. Flash points are normally associated with flammable materials in the liquid phase. By definition, flash point is ‘the lowest temperature at…
url: "https://www.azuvia.co/kb/general-principles/flash-point/"
updated: "2026-11-07"
category: Explosion Proof Basics / General Principles
---

# Flash Point

Flash point is the lowest temperature at which a liquid gives off enough vapour to form an ignitable mixture.

Flash points are normally associated with flammable materials in the liquid phase. By definition, flash point is ‘the lowest temperature at which a material gives off sufficient vapour to form an explosive atmosphere, when tested in a specified test apparatus. This explosive atmosphere can be ignited by an arc, spark or naked flame. Typical examples are given below.

| Fuel Name | Flash point °C |
| --- | --- |
| Benzene | -11 |
| Acetone | -20 |
| Carbon disulphide | -30 |
| Diethyl ether | -45 |
| Gasoline | -46 |
| Paraffin (Kerosene) | 38 |

The flash point of a material gives an indication of how readily that material will ignite in normal ambient temperatures. Different materials have different flash points – most are well below 0°C, but some are well above.

Material with high flash points should not be overlooked as a potential hazard since exposure to hot surfaces can allow a flammable mixture to form locally.

If a flammable material is discharged under pressure from a jet, its flash point may be reduced.

![image of flash point](https://www.azuvia.co/wp-content/uploads/2026/11/flash-point-image.png)

## Using flash point in risk assessment

Flash point is one of the first properties to check when assessing a liquid. A liquid handled above its flash point can form an explosive vapour above its surface, so the area around it may need to be classified. Liquids with flash points below normal ambient temperature, such as gasoline and acetone, are hazardous almost everywhere.

However, a high flash point does not mean no risk. Heating, spraying or releasing a liquid as a mist can create a flammable atmosphere well below its flash point, and hot surfaces can vaporise it locally. Diesel and kerosene, for example, are generally safe at ambient temperature but can form flammable mists under pressure.

Area classification codes therefore consider flash point together with process temperature and the way the liquid may be released. For more detail, read [area classification](/kb/general-principles/basics-on-area-classification/) and [flammable gas table](/kb/general-principles/simplified-flammable-gas-table/). Flash point data for many substances appears in IEC 60079-20-1, published by [IEC](https://www.iec.ch/).