description: "Flameproof electrical protection is essential because Ex d enclosures are tested against gas explosions, not internal short circuits. ## Electrical Protection Flameproof enclosures are tested for their ability to withstand internal gas explosions only; they are not capable of withstanding…"
url: "https://www.azuvia.co/kb/flameproof-ex-d/basics-on-protection/"
updated: "2026-11-07"
category: Explosion Proof Basics / Flameproof (Ex d)
---

# Protection

Flameproof electrical protection is essential because Ex d enclosures are tested against gas explosions, not internal short circuits.

## Electrical Protection

Flameproof enclosures are tested for their ability to withstand internal gas explosions only; they are not capable of withstanding the energy which may be released as a result of an internal short circuit. In order to avoid invalidation of the certification, it is important that properly rated/calibrated electrical protection, e.g. fuses and/or circuit breakers, are utilised.

![electrical protection](https://www.azuvia.co/wp-content/uploads/2026/11/electrical-protection.png)
A Fuse

## Environment Protection

Flameproof machines are not always rain or waterproof. Ingress of rain through joints and gaps can be minimised by using gaskets or ‘O’ rings, which must be part of the design.

Suitable tape can be applied around joints.

## Applying flameproof electrical protection

A flameproof enclosure is designed to survive a gas explosion, not an electrical fault. A sustained short circuit or arc inside can release far more energy, melt the walls or burn through a flamepath. Correctly rated fuses or circuit breakers, chosen to clear faults quickly, are therefore part of the protection and must never be oversized or bypassed.

Water is the other enemy. Flameproof joints are not designed as weather seals, so rain and spray can enter and corrode flamepaths. Only use gaskets, O-rings or non-setting tape where the certificate or manufacturer allows them, because the wrong material can widen the gap or hold the flamepath open.

During inspection, check protection settings, look for corrosion on flamepaths and confirm that any weather protection is approved. For more detail, read [ingress protection methods](/kb/flameproof-ex-d/basics-on-ingress-protection-methods/) and [flameproof cover fasteners](/kb/flameproof-ex-d/basics-on-removable-covers-and-fasteners/). The installation rules come from IEC 60079-14, published by [IEC](https://www.iec.ch/).