# EPL of Ex d Equipment

The Ex d EPL is normally db, which makes flameproof equipment suitable for Zones 1 and 2.

Generally, **Ex d** equipment will have a level of protection **“db”** (EPL: **Mb** or **Gb**).

This means that this equipment can be used in locations requiring EPL Gb or Gc, as indicated on the area classification drawing (in which case a risk assessment, taking into account the possible consequences of an explosion, will have been conducted).
If there are no specified EPL requirements, the equipment may be used in **Zones 1** or **2**

The equipment marking will include the gas subdivision (IIA, IIB or IIC), indicating the gas hazards in which it may be used.

The 2013 edition of the standards also covers levels of protection **“da”** (only applies to catalytic sensors for portable gas detectors), and “dc” (devices or components with switching contacts **– dc** applies to “enclosed break” devices formerly covered under the **Ex n** standard 60079-15)

Level of protection **“da”** has EPL **“Ma”** or **“Ga”** ; “dc” has EPL **“Gc”.**

Other than the specific requirements for level of protection “da” and “dc”, all requirements of the standard apply to level of protection “**db**”.

Flameproof equipment is designed for use with particular Group II gas subdivisions (IIA,IIB and or IIC), and may only be used in the appropriate gas hazards

**Ambient Conditions:**
Unless otherwise marked, flameproof enclosures are designed for use in ambient temperatures in the range -20° to +40°C.

## Selecting by Ex d EPL

Most flameproof equipment is level db, which means EPL Gb. It can therefore be used in Zones 1 and 2, or wherever the area classification drawing calls for Gb or Gc. Level da is limited to special cases such as catalytic sensors in portable gas detectors, while level dc covers small enclosed-break devices formerly certified as type nC.

Gas group is just as important as level. Equipment marked IIB can be used with IIA and IIB gases but not IIC gases such as hydrogen, because their explosions are more severe. Always match the gas group on the label to the hazards on the drawing, and check the temperature class against the ignition temperature of those gases.

Finally, check the ambient range, which is minus 20 °C to plus 40 °C unless otherwise marked. For more detail, read [flameproof protection](/kb/flameproof-ex-d/basics-on-flameproof/) and [Ex equipment selection](/kb/general-principles/basic-on-equipment-selection/). Flameproof equipment is certified through the [IECEx scheme](https://www.iecex.com/).