title: "Ex p[i] (Hybrid)"
description: "Ex p(i) hybrid protection lets associated intrinsically safe apparatus sit in a hazardous area inside a pressurised enclosure. The parts(s) of an IS system which are marked to indicate that they should be installed in a non-hazardous area (associated equipment…"
url: "https://www.azuvia.co/kb/combined-hybrid-methods-of-protection/basics-on-ex-pi-hybrid/"
updated: "2026-11-07"
category: Explosion Proof Basics / Combined (Hybrid) Methods of Protection
---

# Ex p[i] (Hybrid)

Ex p(i) hybrid protection lets associated intrinsically safe apparatus sit in a hazardous area inside a pressurised enclosure.

The parts(s) of an IS system which are marked to indicate that they should be installed in a non-hazardous area (associated equipment **[Ex ia]** etc) may be used in a hazardous area if installed in, for example, a pressurised enclosure as illustrated below.

The enclosure marking would then be of the form **Ex p (ia).** Indicating a pressurised enclosure with an intrinsically safe output.

![ex p[i] (hybrid)](https://www.azuvia.co/wp-content/uploads/2026/11/ex-pi.png)

## Where Ex p(i) hybrid protection is used

Associated apparatus, such as a zener barrier or isolator, is normally installed in the safe area because it is not protected against igniting gas itself. On some sites, however, there is no convenient safe area near the field devices. Placing the associated apparatus inside a pressurised enclosure solves this, because pressurisation keeps flammable gas away from it.

The result is a hybrid marking such as Ex p (ia): the enclosure is protected by pressurisation, and the output circuits leaving it are intrinsically safe. As a result, field wiring can still be treated as IS, with all the benefits for live maintenance. The pressurisation system must, of course, meet the rules for purging, monitoring and action on loss of pressure.

For the two concepts involved, read [pressurised equipment](/kb/pressurisation-ex-p/basics-on-pressurised-equipment/) and [intrinsic safety](/kb/intrinsic-safety-ex-i/basics-on-intrinsic-safety-ex-i/). Hybrid equipment is certified under schemes such as the [IECEx scheme](https://www.iecex.com/), and AZUVIA's [certifications](/about/certifications/) page explains how this applies to our own hazardous-area products.