title: Ex pde (Hybrid)
description: Ex pde hybrid protection covers equipment inside a pressurised enclosure that must stay energised when overpressure is lost. Enclosure using protection by pressurisation type ‘p’, may have internal equipment which have to remain energised in the absence of overpressure. Such…
url: "https://www.azuvia.co/kb/combined-hybrid-methods-of-protection/basics-on-ex-pde/"
updated: "2026-11-07"
category: Explosion Proof Basics / Combined (Hybrid) Methods of Protection
---

# Ex pde (Hybrid)

Ex pde hybrid protection covers equipment inside a pressurised enclosure that must stay energised when overpressure is lost.

Enclosure using protection by pressurisation type ‘p’, may have internal equipment which have to remain energised in the absence of overpressure. Such equipment must be protected in accordance with the Zone in which the enclosure is located. A typical example is an anti-condensation heater within a pressurised machine which will be energised when the machine is idle.

Equipment outside the machine enclosure, e.g. junction boxes, pressure sensors etc., will also have to be protected in accordance with the Zone.

Note: Since anti-condensation heaters are normally ‘live’ when a machine is idle, a notice warning of this danger should be displayed.

![ex pde hybrid](https://www.azuvia.co/wp-content/uploads/2026/11/ex-pde.png)

## Protecting equipment with Ex pde hybrid protection

Pressurisation only protects equipment while overpressure is present. Yet some items must stay energised when the purge air stops. The classic example is an anti-condensation heater in a large motor, which runs when the motor is idle to keep the windings dry. Because overpressure may be absent at that moment, the heater needs its own explosion protection, such as flameproof or increased safety construction.

The same rule applies to anything mounted outside the enclosure, including junction boxes, pressure switches and purge fan motors. Each must be protected for the zone in which it sits. The combined marking, for example Ex pde, shows that the equipment uses pressurisation together with flameproof and increased safety methods.

Finally, remember the people. Because heaters are live when the machine is stopped, a warning notice should say so. For related topics, read [equipment energised without overpressure](/kb/pressurisation-ex-p/basics-on-equipment-energised-during-absence-of-overpressure/) and [externally mounted equipment](/kb/pressurisation-ex-p/basics-on-externally-mounted-electrical-equipment/). Certification of hybrid equipment is covered by the [IECEx scheme](https://www.iecex.com/).